Hello friends!
Delta HMI and Inovance inverter are 2 of the devices commonly used in industry, low price but good quality makes it popular in the market.
Today plc247.com will guide you to use HMI Delta DOP-107EV to control Inovance MD200 inverter using “Modbus RTU” Communication Protocol
HMI Delta & Inovance MD200 “Wiring Diagram”
+ RS485 communication connection diagram between HMI Delta DOP-107EV and Inovance-MD200 inverter.
Inovance MD200 Inverter Parameters Setting
Below are the communication parameters that we need to install for the Inovance MD200 inverter to be able to control it with Modbus RTU.
Inovance MD200 Registers Address
>>> VFD Control Address = 2000 (hexa)
- Set Word “2000” = 1 >>> Forward Run
- Set Word “2000” = 2 >>> Reverse Run
- Set Word “2000” = 6 >>> Stop
>>> Set Frequency Address = 1000 (hexa)
Frequency Reference = (0 to 10000 dec) ~ (0 to VFD Max Frequency)
+ Output Frequency Address = 1001 (hexa)
+ Output Voltage Address = 1003 (hexa)
+ Output Current Address = 1004 (hexa)
Delta DOP-107EV “Modbus RTU” Configuration
We need to configure the communication parameters for the HMI as with the Inovance MD200 inverter.
HMI Programming Example
+ Interface Design
+ Setting Frequency
+ Run Forward
+ Run Reverse
+ Stop
+ Read Output Frequency
+ Read Output Voltage
+ Read Output Current
Video Tutorial
======
References
>>> HMI Delta Programming Software Download
>>> Download Inovance MD200 Manual PDF
Password Extract: plc247.com
Subscribe to Youtube channel and Website to read new articles of plc247.com, please share the article to the community if you find it interesting and useful.
Thanks and Best Regards!